TG 80, TG 81 and TG 82 – diameter 8 mm, -50 °C to 400 °C

These temperature sensors are primarily designed for temperature measurement of solid substances but can also be used for temperature measurement of liquids or gaseous substances. To mount the sensor to the measuring point, a bayonet nut is used that is screwed on a spring. The combination of a bayonet nut, spring and corresponding bayonet connector can provide higher contact pressure of the sensor to the measuring point or correct any changes in the distance between the nut and measuring point during measurement. The maximum temperature range of the sensors is - 50 to 350 °C (short-term 400 ° C). The range for individual design variations is narrowed down by the type of temperature sensing element and supply cable. The sensors meet the level of protection from IP 50 to IP 67 according to EN 60529, as amended, depending on the type of lead-in cable. The sensors are designed to operate in a non-aggressive environment. The method of use must be chosen with regard to temperature and chemical resistance of the case and lead-in cable.

Specification

Sensor type TG 80 TG 81 TG 82
Case end straight semisphere R8 apex 120°
Type of sensing element* all types (Pt 100, Pt 1000, Ni 1000, Ni 10000,Ni 2226=T1, NTC, PTC, KTY, TSiC, DALLAS, TC K, TC J, TC T and so on)
Case material stainless steel DIN 1.4301
Diameter of case 8 mm
Length of case L 10 to 85 mm (with addition of 15 mm for cable attachment)
Lead-in cable variations/ Temperature range
(can be limited by type of sensing element – determine in documentation)
PVC shielded / -30 to 80 °C
PVC unshielded / -40 to 105 °C
silicone shielded / -50 to 200 °C
teflon shielded / -50 to 250 °C
with fibreglass (with metal braiding) / 0 to 350 °C (for short term 400 °C)
Ingress protection PVC and silicone cables IP 67
teflon cables IP 64
cables with glass fibre IP 50

acordance with EN 60529, as amended
Material / Dimension of bayonet nut nickel-plated brass / L = 18 mm, inner Ø 15 mm
Material / Dimension of spring stainless steel DIN 1.4301 / L = 200 mm, outer Ø 8 mm, Ø of wire 0.9 mm
Insulation resistance 200 MΩ at 500 V DC
Maximum permissible static pull on the lead-in cable 1 kg

*) Certain technical specifications of thermocouple sensors (lead wires, IP rating, etc.) may differ with different types.
Note: Manufacturer reserves the right to make changes in design and technical characteristics of the products. For actual information, please always contact your dealer.

Dimensional Draft

Wiring Diagram

Visit our downloads page to view technical characteristics or contact our technical sales department for more information, prices or with your specifications.

Also, you can reach us on +44 (0) 1865400514
We use cookies to deliver you the best experience. By browsing our website you agree to our use of cookies. Learn More